LOK16系列燃油燃烧器控制器
品牌:SIEMENS(西门子)
产地:德国
|
产品介绍 |
Burner controls type LOK16... feature a self-checking flame supervision circuit. That supervision circuit initiates the required safety actions not only in the case of premature or missing flame signals, but also in the event of any kind of fault on the flame detector, the detector cables or the flame signal amplifier that could simulate a flame signal during burner operation.
The burner controls are therefore suited for use in all types of oil-fired combustion plants where self-checking flame supervision systems are either mandatory or recommendable:
-
Burners that operate continuously
-
Burners in intermittent operation that, in the case of great heat demand, may operate continuously for more than 14 hours, e.g. in plants using boiler sequencing
-
Burners that need to comply with the German TRD 411 and TRD 412 regulations for steam boilers
-
Burners in plants where, for specific safety requirements, supervision of the burner by a self-checking flame supervision system seems advisable
|
型号表 |
|
LOK16.140A27 |
LOK16.250A27 |
LOK16.650A27 |
注释 |
快速式 |
通用式 |
重油式 |
t1 |
10 |
22.5 |
67.5 |
预吹扫时间(风门全开时) |
TSA |
4 |
5 |
5 |
安全时间 |
TSA’ |
- |
- |
- |
安全时间 |
t3 |
2 |
2.5 |
2.5 |
预点火时间 |
t3’ |
从启动命令开始(如果带有空气压力监测,从接受到空气压力监控信号开始) |
长预点火时间 |
t3n |
10 |
15 |
15 |
后点火时间(点火变压器连接端口15) |
t4 |
8 |
7.5 |
7.5 |
从TSA开始到端口19的阀打开的间隔时间 |
t4’ |
- |
- |
- |
从TSA开始到端口19的阀打开的间隔时间 |
t5 |
4 |
7.5 |
7.5 |
从t4结束到比例调节或端口20的阀门打开的间隔时间 |
t6 |
10 |
15 |
15 |
后吹扫时间 |
t7 |
2 |
2.5 |
2.5 |
打开风机马达2的延迟时间 |
t8 |
30 |
47.5 |
92.5 |
没有t11和t12时,整个启动阶段时间 |
t9 |
- |
- |
- |
第二安全时间 |
t10 |
6 |
10 |
10 |
从启动到空气压力监测开始工作的间隔时间 |
t11 |
Optional |
风门打开到最大位置的时间 |
t12 |
Optional |
风门至小火位置的时间 |
t13 |
|
|
|
可允许的燃烧后时间 |
t16 |
4 |
5 |
5 |
从启动到风门打开命令的间隔时间 |
t20 |
32 |
35 |
12.5 |
锁定后程序内部循环时间 |
类似型号 |
LAL2.14 |
LAL2.25 |
LAL2.65 |
|
|
|
技术参数 |
主要参数 |
主电压 |
AC220V -15%...AC240V +10% |
AC100V -15%...AC110V +10% |
主频率 |
50...60Hz ±6% |
外部保险丝 |
16A |
功率 |
3.5VA |
重量 |
1000g(底座165g) |
保护等级 |
IP40 |
|
|
环境条件 |
运输环境 |
IEC 60 721-3-2 |
内部条件 |
class 2K2 |
温度范围 |
-50...+60ºC |
机械条件 |
class 2M2 |
湿度 |
<95% |
运行环境 |
IEC 60 721-3-3 |
内部条件 |
class 3K5 |
机械条件 |
class 3M2 |
温度范围 |
-20...+60ºC |
湿度 |
<95% |
不得进水 |
|
|
免责声明:以下信息由企业自行提供,内容的真实性、准确性和合法性由发布企业负责。锅炉信息网对此不承担任何保证责任。